• Profibus

Communication Module SPI - PROFIBUS DP Slave

The module for all communication tasks

Product Image

COMX 52CA-DPS-Image

COMX 52CA-DPS

Active

At a glance

  • Complete slave interface with network connector onboard
  • Host connection via dual-port memory or SPI
  • Allows one baseboard design for all networks
  • Function compatible replacement for comX 10CA-DPS

Weitere Informationen

Description

The module for all communication tasks

The comX communication module has been designed to be integrated into automation devices e.g. robot controllers, PLCs or drives to add a network interface. All communication tasks are executed autonomously within the module - irrespective of the processor of the target device.

Process data is exchanged via a Dual-Port-Memory which is accessed either by an 8-/16-bit bus interface or a fast 50 MHz SPI interface.

comX supports all major Real-Time Ethernet protocols as Master or Slave and covers all network-specific demands in just one single module. To support a line topology, the module is equipped with two Ethernet ports. The communication protocol can be changed simply and reliably by loading the appropriate firmware and a software license for masters.

Due to the Hilscher network controller netX, a 10-years delivery guarantee is granted.

Technical Details

COMX 52CA-DPSParameterValue
ProductPart number1581.420
DescriptionCommunication module PROFIBUS DP Slave
Communication controllernetXnetX 52
Integrated memoryFlash4 MB SPI Flash EPROM
Voltage/power supplySupply voltage+3.3V DC ± 5%
Typical/maximum current consumption400 mA / 440 mA (at 3.3 V)
In case of a short circuit of the 5 V PROFIBUS supply, the current consumption increases by further approx. 70 mA.
Typical power consumptionApprox. 1.35 W (at 3.3 V)
ConnectorVia system bus interface X1
System interfaceTypeParallel or serial dual-port memory interface
Connector50-pin SMT connector, socket
Pin distance1.27 mm
Dual-port memory size16 KB (lower 8 KB used by firmware)
Data width8/16 bit, switchable
Serial dual-port memory interfaceSPI slave, mode 3
Baud ratemax. 50 MHz
Communication interfaceCommunication standardPROFIBUS DP Slave
Interface typeRS-485, isolated
ConnectorD-Sub socket, 9-pin
Transmission rate9.6 kBits/s, 19.2 kBits/s, 31.25 kBits/s, 45.45 kBits/s,93.75 kBits/s, 187.5 kBits/s, 500 kBits/s,1.5 MBits/s, 3 MBits/s, 6 MBits/s, 12 MBit/s
Auto detectionYes
Diagnostic interfaceTypeUART or USB
ConnectorSignal on the host interface. Available only if integrated with host system.
DisplayLED displaySYS system status, green: RUN, yellow: RDY
COM communication status, green: RUN, red: ERR
Operating elementsNetwork address2 rotary switches for address
EnvironmentOperating temperature range-20 °C … +70 °C (Air flow during measurment: 0.5 m/s)
Temperature range for storage–40 °C … +85 °C
Humidity range10 % ... 95 % relative humidity (non-condensing)
DeviceDimensions (L x W x H)70 mm x 30 mm x 21.5 mm
Weightapprox. 35 g ... 40 g
MountingUsing screwable metal bolts, according to comX Design Guide
ConfigurationConfiguration softwareSYCON.net
ComplianceRoHSYes
Compliance with EMC guidelinesCE markingYes
UKCA markingYes
EmissionEN 61000-6-4
ImmunityEN 61000-6-2
Electrostatic discharge (ESD) according to EN 61000-4-2:2009-12 (Air discharge method)± 8 kV, criterion A
Electrostatic discharge according to EN 61000-4-2:2009-12 (Contact discharge method)± 6 kV, criterion A
Fast transient interferences (burst) according to EN 61000-4-4:2013-04± 2 kV, criterion A (communication lines, shielded)
Surge voltages according to EN 61000-4-5:2019-031 kV, criterion A (communication lines, shielded)

Ordering information

Product namePart numberBrief description
COMX 52CA-DPS1581.420/DPSCommunication Module SPI - PROFIBUS DP Slave

Accessories

Product namePart numberBrief description
COMXEB1530.000comX Evaluation Board
CIF 50-CB-COM-ABC1059.000PCI Evaluation Hardware for comX and COM-C
CIF 50-DB-COM-CA1059.010PCI Evaluation Hardware for comX and COM-C

The comX communication module is a universal solution for upgrading devices with master or slave functionality. All modules are pin-compatible and have an identical software interface.
There are designs with an integrated network connector and designs in which the network interface is tied to the base board.

Brochures, Whitepaper and Case Studies

Find all our current Media to Embedded Modules at our Media Archive.