NT 50-DP-EN
Gateway PROFIBUS DP to Ethernet

Cost-optimized entry level gateway for simple conversions
  • Integrates a PROFIBUS DP Slave into an Ethernet network, and vice versa

  • Short I/O data conversion period of less than 20 ms

  • Space-saving, compact design

  • Loadable firmware enables a flexible use - also for dual slave conversions

  • With diagnosis and configuration interface via Ethernet

netTAP 50 connects to communication networks and acts as a Gateway for simple conversions between one Real-Time Ethernet protocol (1-port) and one fieldbus protocol or one serial automation protocol as well as between one fieldbus protocol and one serial automation protocol. netTAP 50 supports Slave-zu-Slave- and Slave-zu-Master-conversions. As a master, netTAP 50 provides only one single slave device with the full master function. This makes it easy to integrate a single field device into any higher-level network.

The design of the netTAP 50 convinces by its compact hardware and is reduced to the basic requirements of a protocol converter. The converter is directed to market segments for which the factor costs has priority. This makes the netTAP 50 an attractively priced and universally applicable gateway that offers a wide variety of conversion options.

Product

Product name

NT 50-DP-EN

Part number

1758.110

Brief description

Gateway PROFIBUS DP to Ethernet

Communication controller

Communication controller

netX 50

Integrated Memory

RAM

8 MB SDRAM

FLASH

4 MB serial Flash

Power supply

Supply voltage

24 V ± 6 V DC

Current consumption at 24 V (typically)

72 mA / 150 mA (with short circuit at the output of PROFIBUS)

Typical power consumption

1,8 W

Connector type

Mini-COMBICON, 2-pin

Communication interface X2

Communication interface

PROFIBUS DP

Interface type

RS-485, optically isolated

Connector type

D-Sub female, 9-pin

Communication interface X3

Communication interface

Ethernet

Interface type

10BASE-T/100BASE-TX, isolated

Connector type

1 * RJ45

Diagnostic interface

Type

Ethernet, 4-pin

Connector type

RJ45 socket

Display

LED displays

SYS System status

APL Application status

COM Communication status

LINK Link, ACT Activity

Permitted ambient conditions

Ambient temperature (operation)

0 °C … +55 °C

Ambient temperature (storage)

-40 °C … +85 °C

Relative humidity

10 % … 95 %, non-condensing

Altitude

0 m … 2000 m

Device

Dimensions (L x W x H)

100 x 26 x 66 mm (without connector)

Weight

appr. 80 g

Degree of protection

IP 20

Mounting type

on DIN rail EN 60715

Configuration

Configuration software

SYCON.net

Conformity

RoHS

Yes

Conformance with EMC directives

CE sign

Yes

UKCA sign

Yes

Emission

EN 55011 / BS EN 55011

Immunity

EN 61131-2 / BS EN 61131-2

Product name

Part number

Brief description

NT 50-DP-EN

1758.110