Logo Hilscher

Technologies

  • EtherCAT
  • EtherNet/IP
  • PROFINET
  • Sercos
  •  

Gateway Real-Time Ethernet Slave to Real-Time Ethernet Slave

Bridging between two Real-Time Ethernet networks

Product Image

 

NT 151-RE-RE-Image

NT 151-RE-RE

Active

At a glance

  • Flexible loadable for PROFINET, EtherCAT, Sercos, EtherNet/IP and POWERLINK
  • Effortless network integration as standard I/O slave device both-ways
  • Shortest I/O data conversion time lower than 10 ms
  • Secure network segregation via data buffer
  • Device replacement in seconds via memory card based loading
  • With USB diagnostic and configuration port

Weitere Informationen

Description

The gateway netTAP 151 transmits IO data bidirectionally between any two industrial Real-Time Ethernet networks. It is the ideal solution for installations with heterogenous networks or such of the same kind to exchange data across given network boundaries. With more than 25 different combinations of the protocols PROFINET, EtherCAT, EtherNet/IP, POWERLINK and Sercos, the device series provides a solution for any conversion.

The integration as simple IO device into the primary network makes the converter compatible with any common PLC. On the secondary side it works either as IO device too or controls a subordinate network as a bus master. The length of the IO data can be scaled to any application and the data in between can be mapped on byte level arbitrarily.

Secure network separation is provided by two Ethernet controllers, each connected to a Dual Ethernet port with integrated switch. That allows realizing star, ring and inline network topologies without further peripherals. Both controllers handle the protocols independent from each other and exchange only the IO data across a data buffer. An overall data processing time lower than 10 milliseconds is achieved.

The devices can be ordered preloaded with firmware and license or unloaded. Unloaded devices minimize the storage costs. Subsequent loading of a firmware configures these devices for any conversion most flexible. All devices are commissioned and diagnosed network independent over USB.

Technical Details

NT 151-RE-RE Parameter Value
ProductPart number1722.122
Brief descriptionGateway Real-Time Ethernet Slave to Real-Time Ethernet Slave
Communication controllerPrimary network X2 / Secondary network X3netX 51 / netX 100
Integrated MemoryRAMnetX 51: 8 MB SDRAM, netX 100: 8 MB SDRAM
FLASHnetX 51: 4 MB serielles Flash, netX 100: 4 MB serielles Flash
SD memory card (optional)max. 2 GByte, do not use SDHC or SDXC card types
Power supplySupply voltage24 V DC ± 6 V
Current at 24 V (typically)190 mA
Power consumption4.78 W
ConnectorMINI COMBICON, 5-pin
Reverse voltage protectionyes
Communication interface X2Communication standardEthernet
Interface type100BASE-TX, isolated
Connector2 * RJ45
Auto negotiationsupported
Auto cross oversupported
Communication interface X3Communication standardEthernet
Interface type100BASE-TX, isolated
Connector2 * RJ45
Auto negotiationsupported
Auto cross oversupported
Diagnostic interfaceTypeUSB
ConnectorMini-USB, 5-pin
DisplaysLED displaysSYS system status
APL application status
COM0, COM1, COM2, COM3 protocol specific communication status
4 x LINK (RJ45)
4 x ACT (RJ45)
Permitted ambient conditionsAmbient temperature range for operationIf distance to neighboring devices is minimum 17.5 mm: -20 … +60°C; If housing has contact to neighboring device (and if surface temperature of neighboring device does not exceed +70°C): -20 … +50°C
Humidity10 ... 95 %, no condensation permitted
DeviceDimensions (L x W x H)113.6 mm x 22.6 mm x 99 mm (without connector)
Weight121 g
Degree of protectionIP20
MountingTop hat rail (DIN rail EN 60715)
ConfigurationSoftwareSYCON.net
ConformityRoHSYes
Conformance with EMC directivesCE signYes
ESD Air discharge (DIN EN 61000-4-2)8 kV (criterion A)
ESD contact discharge (DIN EN 61000-4-2)6 kV (criterion A)
Immunity: radiated, HF field (DIN EN 61000-4-3) 80 MHz ... 3 GHz10 V/m (criterion A)
Burst (DIN EN 61000-4-4)2.2 kV (criterion B)
Surge (DIN EN 61000-4-5)1 kV (criterion A)
Immunity: conducted (DIN EN 61000-4-6) 150 kHz ... 80 MHz10 V/m (criterion A)
Radio interference emission (DIN EN 55016-2-3)30 ... 2000 MHz (criterion A)
Radio interference voltage (DIN EN 55016-2-1)0.01 ... 30 MHz (criterion A)

Ordering information

Product name Part number Brief description
NT 151-RE-RE1722.122Gateway Real-Time Ethernet Slave to Real-Time Ethernet Slave

The netTAP 151 transmits data between two Real-Time Ethernet networks. It is the ideal solution to exchange data across network boundaries. With more than 25 combinations of the protocols PROFINET, EtherCAT, EtherNet/IP, POWERLINK and Sercos, the device series provides a solution for any conversion.

Reduce the range of devices with the following protocol filters