A netHOST RTE is a full-featured and autonomously operating Real-Time Ethernet master allowing industrial PCs and other embedded systems the control of Real-Time Ethernet networks over an ordinary LAN connection.
A simple TCP/IP based transport protocol transfers the services between the controlling unit and the device. For device integration a DLL for Windows and a ‚C‘ source code for embedded solutions is provided. In both cases the call interface (API) is identical to Hilschers PC cards. This makes a netHOST a „remotely controllable PC card forield installations“.
100 bytes process data inputs and outputs are exchangeable over the LAN network in about one millisecond.
Acyclic services to the subordinate Real-Time Ethernet stations are supported as well. A bus configuration software is included in the delivery. Two devices can be used in combination to realize redundant applications. Services are provided to execute a controlled switchover in the event one device fails or a line breaks. In case a device fails the memory card slot allowservice personnel to perform a firmware and configuration recovery on a replacement device in less than a minute.
Product | Product name | NHST-T100-EN/PNM |
Part number | 1890.840 | |
Brief description | Ethernet LAN PROFINET IO-Controller | |
Communication controller | netX | netX 100 |
Integrated Memory | RAM | 8 MB SDRAM |
FLASH | 4 MB serial Flash | |
Memory card | Type and size | SD card, max. 2 GByte. SDHC- or SDXC-card type must not be used. |
Power supply | Supply voltage | 24 V DC ± 6 V |
Maximum Current at 24 V (typically) | 130 mA | |
Typical power consumption | 3,2 W | |
Connector | Mini-COMBICON, 2-pin | |
Reverse voltage protection | yes | |
Requirement to the power supply | For UL conform usage: Device shall be supplied by an isolated voltage source | |
Communication interface 1 | Communication standard | Ethernet |
Interface type | 100BASE-TX or 10BASE-T, isolated | |
Connector | 2 * RJ45 | |
Communication interface 2 | Communication standard | Ethernet |
Interface type | 100BASE-TX or 10BASE-T, isolated | |
Connector | 1 * RJ45 | |
Diagnostic interface | Type | USB |
Connector | Mini-USB, 5-pin | |
Displays | LED displays | SYS System status netHOST |
APL Application status netHOST | ||
SF Communication status | ||
BF Communication status | ||
LINK Link | ||
ACT Activity | ||
Environment | Ambient temperature range for operation | 0 … +60 °C |
Humidity range | no condensation permitted | |
Pollution degree | For UL-compliant usage: Device must be used in a pollution degree 2 environment | |
Device | Dimensions (L x W x H) | 100 x 52 x 70 mm (without connector) |
Weight | appr. 150 g | |
Degree of protection | IP 20 | |
Mounting | on DIN rail EN 60715 | |
Configuration | Configuration software | SYCON.net |
Ethernet Device Configuration Tool | ||
Conformity | RoHS | Yes |
Conformance with EMC directives | CE sign | Yes |
Emission | CISPR 11 Class A | |
Immunity | EN 61131-2:2003 |
Product name | Part number | Brief description |
---|---|---|
NHST-T100-EN/PNM | 1890.840 | Ethernet LAN PROFINET IO-Controller |
Documentations overview
Configuration software
User manual
Devices of the netHOST class serve to control Fieldbus or Real-Time Ethernet systems over conventional Ethernet.
They are used in conjunction with compact industrial PCs or embedded systems having Ethernet interfaces only instead of PC card slots.