NFD-6090-PNS-IOLMA\M12
Active

netFIELD IO-Link Master Class A PROFINET IO-Device

IO-Link Master in the industrial network
  • Real-Time Ethernet - IO-Link gateway

  • Compatible with IO-Link standards of comparable performance

  • Supports up to 8 IO-Link Devices simultaneously

  • Range of point-to-point communication up to 20 m

  • IO-Link Configuration Tool

  • Robust IP67 design - No ingress of dust or water

netFIELD Device is an IP67-protected device and ready for immediate use. As a part of the comprehensive netFIELD solution portfolio for your IIoT environments, netFIELD device provides an ideal technology platform and software ecosystem for Real-Time Ethernet IO-Link applications. netFIELD Device is optimized for brand labeling.

Machine engineers and systems integrators can provide their devices that are equipped with netFIELD Devices additionally with IO-Link sensors and integrate the sensors easily and reliably into industrial networks. IO-Link is a standard for data communication at the field level as well as for the communication of sensors and actuators. The possibility to configure these components automatically facilitates the installation of your devices. The easy connection of IO-Link sensors enables you to benefit from an accelerated commissioning as well as from reduced costs due to shorter downtimes in case of an error.

Moreover, the netFIELD Device technology platform enables you to benefit from the entire Hilscher ecosystem with regular and pre-tested firmware updates, pre-certified protocol stacks, optional workshops, and software adaptations.

Category

Parameter

Value

Product

Part number

1913.100

Name

NFD-6090-PNS-IOLMA\M12

Function

PROFINET IO-Device / 8 Port IO-Link Master

Power supply 1L, 2L

Supply voltage 1L, 2L

24 V DC, –25%/+30% (18 V DC … 31.2 V DC)

Voltages higher than 34 V can damage the device permanently.

Voltages below approx. 11 V result in a device reset.

Low voltage warning 1L

18.0 V (± 5% at 25 °C) notification on,

18.3 V (± 5% at 25 °C) notification off

Overvoltage warning 1L

30.0 V (± 5% at 25 °C) notification on,

29.7 V (± 5% at 25 °C) notification off

Current consumption

1L: 0.1 A ... 16 A (at 24 V DC)

2L: 0.01 A ... 16 A (at 24 V DC)

Current consumption of supply port

Max. 16 A, consider external limitation or use fuse in the supply line.

Maximum total current including transit between the current connector pins may not exceed 16 A for each 1L and 2L. If additional devices are connected to X32 (PWR OUT), then the maximum total current if necessary has to be monitored by an external power management.

Maximum current: Observe the derating depending on the ambient temperature.

Conductor cross-section

0.5 mm2 … 2.5 mm2

Observe the current carrying capacity and cable length!

Connector

PWR IN: M12 L-coded, 5-pin, plug

PWR OUT: M12 L-coded, 5-pin, socket

Torque

1.0 Nm

Reverse polarity protection

Yes

Power supply

24 V DC PELV (Protective Extra Low voltage) or SELV (Safety Extra Low voltage) power supply

Total load

Maximum total load current (total of all currents of ports X1 - X8)

15.7 A

Device

Dimensions (L x W x H)

200 mm x 60 mm x 32 mm

Weight

404 g

Housing

Plastic

Potting

Solvent-free electro-casting resin system based on 2 K polyurethane

Protection class

IP67 (EN 60529)

Protection class

III (EN 61140)

Mounting

Screw mounting on carrier, 2x M4

Environmental conditions

Location of operation

Indoor

Ambient temperature (operation)

–25 °C … +70 °C

Ambient temperature (storage)

–40 °C … +80 °C

Maximum temperature change

3 K / min

Relative humidity

5% … 95%

Degree of pollution

3 (EN 60664-1)

Altitude

0 … 2000 m

Overvoltage category

II (EN 60664-1)

Degree of protection

IP67 (EN 60529)

Protection class

III (EN 61140)

Electrical safety

Insulation resistance

60 V DC

Test voltage

550 V AC RMS

Min. creepage distance

0.7 mm

Ethernet connector

Communication interface

Ethernet

Autonegotiation, autocrossover

Yes

Connector

2x M12, D coded, socket, 4-pin

Torque

1.0 Nm

IO-Link connector

Connector

8x M12, A coded, plug, 5-pin

Torque

1.0 Nm

Operating modes

Pin 2: DI or DO

Pin 4: IO-Link Master, DI or DO

Displays

SYS

System status, green/yellow

APL

Application status, red/green

SF

System error (PROFINET), red

BF

Bus error (PROFINET), red

LINK

Link status, green

ACT

Activity status, yellow

1L, 2L

Supply voltage status, red/green

A, B

Port status: red/green/yellow (yellow by simultaneous red and green)

Compliance

RoHS

Yes

Compliance with EMC guidelines

CE sign

Yes

UKCA sign

Yes

Emission

EN 61000-6-4 / BS EN 61000-6-4

Immunity

EN 61000-6-2 / BS EN 61000-6-2

Product name

Part number

Brief description

NFD-6090-PNS-IOLMA\M12

1913.100

netFIELD IO-Link Master Class A PROFINET IO-Device