NT 50-CO-RS
Active

Gateway CANopen to Serial (ASCII) or Modbus RTU

Cost-optimized entry level gateway for simple conversions
  • Integrates a Modbus RTU device into a CANopen network, and vice versa

  • Integrates ASCII-protocol-supporting devices as nodes in CANopen

  • Space-saving, compact design

  • Loadable firmware for the flexible use of further conversions

  • With diagnosis and configuration interface via Ethernet

netTAP 50 connects to communication networks and acts as a Gateway for simple conversions between one Real-Time Ethernet protocol (1-port) and one fieldbus protocol or one serial automation protocol as well as between one fieldbus protocol and one serial automation protocol. netTAP 50 supports Slave-zu-Slave- and Slave-zu-Master-conversions. As a master, netTAP 50 provides only one single slave device with the full master function. This makes it easy to integrate a single field device into any higher-level network.

The design of the netTAP 50 convinces by its compact hardware and is reduced to the basic requirements of a protocol converter. The converter is directed to market segments for which the factor costs has priority. This makes the netTAP 50 an attractively priced and universally applicable gateway that offers a wide variety of conversion options.

Product

Product name

NT 50-CO-RS

Part number

1756.100

Brief description

Gateway CANopen to RS-232/422/485

Communication controller

Communication controller

netX 50

Integrated Memory

RAM

8 MB SDRAM

FLASH

4 MB serial Flash

Power supply

Supply voltage

24 V ± 6 V DC

Current consumption at 24 V (typically)

72 mA

Connector type

Mini-COMBICON, 2-pin

Communication interface X2

Communication interface

CANopen

Interface type

ISO 11898, optically isolated

Connector type

D-Sub male, 9-pin

Communication interface X3

Communication interface

Serial interface

Interface type

RS-232, RS-422, RS-485

Connector type

RJ45, Ethernet and serial interface together in one connector

Diagnostic interface

Type

Ethernet, 4-pin

Connector type

RJ45 socket

Display

LED displays

SYS System status

APL Application status

COM Communication status

LINK Link, ACT Activity

Permitted ambient conditions

Ambient temperature (operation)

0 °C … +60 °C

Ambient temperature (storage)

-40 °C … +85 °C

Relative humidity

10 % … 95 %, non-condensing

Altitude

0 m … 2000 m

Device

Dimensions (L x W x H)

100 x 26 x 66 mm (without connector)

Weight

appr. 80 g

Degree of protection

IP 20

Mounting type

on DIN rail EN 60715

Configuration

Configuration software

SYCON.net

Conformity

RoHS

Yes

Conformance with EMC directives

CE sign

Yes

Emission

EN 55011 / BS EN 55011

Immunity

EN 61131-2 / BS EN 61131-2

Product name

Part number

Brief description

NT 50-CO-RS

1756.100

Gateway CANopen to Serial (ASCII) or Modbus RTU