NHST-T100-DP/DPM
Ethernet LAN PROFIBUS DP Master

LAN-controlled PROFIBUS DP Master for the DIN rail
  • Full-featured DP/DPV1 Master for up to 125 PROFIBUS Slaves

  • Open access per TCP/IP-based access protocol

  • Quick start per DLL with uniform API to cifX PC cards

  • Simple integration into embedded systems per driver in "C" source code

  • Open, XML-based configuration possibility

  • Supports master services of class 1 and 2

A netHOST FB is a full-featured and autonomously operating Fieldbus master that enables industrial PCs and embedded systems to control Fieldbus networks via a standard LAN connection.

A simple TCP/IP-based transport protocol transfers the services between the controlling unit and the device. A Windows DLL and a “C” source code for embedded solutions are provided for device integration. In both cases the application interface (API) is identical with the PC cards from Hilscher. The application interface thus makes the netHOST for existing applications a “remotely controllable PC card for field installations”.

100 bytes process data inputs and outputs can be transmitted via the LAN network in about one millisecond. Acyclic services to the subordinate Fieldbus stations are supported as well. The bus configuration software is included within the delivery.

Owing to the LAN technology, two devices can be operated in combination as redundant devices. If one of the two devices fails or if a line is interrupted, switching over from one device to the other is possible.

Within seconds, the maintenance personnel can use the memory card slot and a memory card to load and commission a replacement device without any additional software.

Product

Product name

NHST-T100-DP

Part number

1890.410

Brief description

Ethernet LAN PROFIBUS DP Master

Communication controller

netX

netX 100

Integrated Memory

RAM

8 MB SDRAM

FLASH

4 MB serial Flash

Memory card

Type and size

SD card, max. 2 GByte. SDHC- or SDXC-card type must not be used.

Power supply

Supply voltage

24 V DC ± 6 V

Maximum Current at 24 V (typically)

130 mA

Typical power consumption

3,2 W

Connector

Mini-COMBICON, 2-pin

Reverse voltage protection

yes

Requirement to the power supply

For UL conform usage: Device shall be supplied by an isolated voltage source

Communication interface 1

Communication standard

Ethernet

Interface type

100BASE-TX or 10BASE-T, isolated

Connector

2 * RJ45

Communication interface 2

Communication standard

PROFIBUS-DP

Interface type

RS-485, optically isolated

Connector

D-Sub, female, 9-pin

Diagnostic interface

Type

USB

Connector

Mini-USB, 5-pin

Displays

LED displays

SYS System status

APL Application status

COM Communication status

LINK Link, ACT Activity

Environment

Ambient temperature range for operation

0 °C … +60 °C

Ambient temperature range for storage

-40 °C … +85 °C

Humidity range

no condensation permitted

Pollution degree

For UL-compliant usage: Device must be used in a pollution degree 2 environment

Altitude

0 m … 2000 m

Device

Dimensions (L x W x H)

100 x 52 x 70 mm (without connector)

Weight

appr. 150 g

Degree of protection

IP 20

Mounting

on DIN rail EN 60715

Configuration

Configuration software

SYCON.net

Ethernet Device Configuration Tool

Conformity

RoHS

Yes

Conformance with EMC directives

CE sign

Yes

UKCA sign

Yes

Emission

EN 55011 / BS EN 55011

Immunity

EN 61131-2 / BS EN 61131-2

Product name

Part number

Brief description

NHST-T100-DP/DPM

1890.410

Ethernet LAN PROFIBUS DP Master